Savant Power System Compatibility Reference Guide

 

Document Date:December 2025

 

Overview

This document details compatibility and feature support considerations for first and third party battery storage solutions integrated with a Savant Power System.

 

 

Supported Savant Power Storage (PS20 / PS50) Configurations

The Savant Power Storage 20 and Power Storage 50 energy storage system (ESS) inverter and battery solutions support the widest range of features and configurations available when combined with a Savant smart panel (Power Director and Power Modules) or when integrated with a Savant smart home (Savant Host with Power Modules and Panel Bridge).

 

 

Partial and Whole Home Backup

Savant Power Storage supports partial and whole home backup configurations.

 

Solar

Savant Power Storage supports both DC coupled solar (up to 17kW each) and AC coupled solar (up to 12.5kW)*.

*See Power Storage 20 / Power Storage 50 Installation Manual for full DC and AC coupled solar design considerations.

 

Generator

Savant Power Storage supports AC standby hardwired generators with 2-wire start/stop capability.

NOTE: Portable generators are not supported at this time.

 

Generator ATS

The Generator ATS must have auxiliary (NC/NO) contacts to determine ATS position (only applicable when generator and grid are combined into the inverter GRID port).

IMPORTANT NOTE:

  • An added generator ATS is only required if the generator is landed on the grid input of Power Storage Inverter.

 

Solar Rapid Shutdown

Rapid shutdown devices that are certified with SunSpec are supported. Savant has tested with APSmart and Tigo TS4-F devices.

 

Battery

  • Each battery stack requires at least 1 inverter. For additional solar and passthrough capability, up to 2 inverters can share 1 battery stack.
  • Each battery stack must be populated with all battery modules (8 battery modules for PS20, 10 battery modules for PS50).

 

Scalability

Up to ten (10) Power Storage Inverters can be stacked in parallel for a single deployment. The solution will support up to 10 Power Storage 20 or 10 Power Storage 50 battery stacks. For larger systems, contact Savant Support.

 

Three Phase

Savant Power Storage does not support three phase capability at this time.

 

Network

Deployment of a Savant Power Storage system requires an onsite internet connection. Savant strongly recommends hardwiring the network connection for best results. In cases where Wi-Fi must be used, Savant recommends running ethernet cable temporarily for initial setup/firmware updates.

 

Savant App & Load Management Compatibility – Requires Power Director or Savant Host

Power Storage Inverter and Power Director communicate locally over TCP/IP. All communication is locally authenticated and encrypted.

 

 

Third Party Compatibility

The following battery solutions support integration with the Savant Power System.

 

Tesla

  • Powerwall 2 with Backup Gateway 2
  • Powerwall + with Backup Gateway 2 or Backup Switch
  • Powerwall 3 with Backup Gateway 2 or Backup Switch

 

FranklinWH

  • aPower X with aGate

 

Enphase IQ Battery

  • IQ Battery 3
  • IQ Battery 3T
  • IQ Battery 10
  • IQ Battery 10T
  • IQ Battery 5P
  • IQ Battery 10C

Sol-Ark

  • Sol-Ark 12K
  • Sol-Ark 15K 
  • Sol-Ark 18K

    NOTE: Must use Sol-Ark supported third party batteries and batteries must communicate via CAN bus, as Modbus is utilized for the Savant Load Management integration.

 

 

 

System Communication Requirements

In order for the Savant Power Director to integrate with third-party battery storage solutions, the Power Director and the battery inverter must communicate using the the Local Area Network or Power Director’s Local Access Point. The following types of communication are required depending on system type:
 

 

BatteryInverter Aux Contact -> Director GPIO (Grid State)Cloud or Local APICommunication: RS-485 or Ethernet or Director APSavant Host & Controller RequirementNotes

Tesla

RecommendedLocalEthernet (wired direct or through external switch) or via Director Access PointSavant Host or Power DirectorRequires Tesla Gateway/Controller Username & Password
Franklin

Not supported

Cloud (Local API coming soon)Battery, inverter, and Power Director must to be connected to the same Local Area Network.Savant Host or Power DirectorN/A
Enphase

Required

Local

Ethernet (wired direct or through external switch) or via Director Access Point (Note: Checking in QA before we publish)

Savant Host or Power Director

Requires Enphase Username & Password
Sol-Ark

N/A

Local

RS-485

  • Savant Host and 1x SSC-002485
    NOTE: Add 1x SSC-002485 for every 2 additional Sol-Ark inverters
  • Power Director
    NOTE: Add 1x SSC for more than 2 Sol-Ark inverters, 1 needed for every 2 Sol-Ark inverters
 

 

 

Third Party Battery Energy Monitoring

The Power Director receives information on the total consumption of the main feed, battery power, generator, and solar power from the battery inverter and reports it to the Savant app. In this case, the Current Track Module or Smart Energy Monitor is not required to monitor the main feed or power sources. However, a Current Track Module or Smart Energy Monitor can be used to monitor loads in the system that are not monitored by the inverter or Savant Power Modules.

 

 

Power Module to Panel Compatibility

 

Power Module
Model
Supported PanelsSupported Neutral Connection TypePower Module 20A SKUPower Module 30A SKUPower Module 60A SKUCurrent Track Module SKU
QO PON Power ModuleSquare D QOPlug-on NeutralGPM-QP2R20120-21 GPM-QP1R30240-21 GPM-QP1R60240-21 None
QO Pigtail Power ModuleSquare D QOPON or non-PONGPM-Q2R20120-21 GPM-Q1R30240-21 GPM-Q1R60240-21 GPM-Q2SEM-00 
CH PON Power ModuleEaton Cutler-Hammer Plug-on NeutralGPM-CP2R20120-21 GPM-CP1R30240-21 GPM-CP1R60240-21 None
CH Pigtail Power ModuleEaton Cutler-Hammer PON or non-PONGPM-C2R20120-21 GPM-C1R30240-21 GPM-C1R60240-21 GPM-C2SEM-00 
1-inch Pigtail Power ModuleSchneider Homeline, Eaton BR, Siemens PN/SN/Murray, ABB/GE PowerMark GoldPON or non-PONGPM-H2R20120-21 GPM-H1R30240-21 GPM-H1R60240-21 GPM-H2SEM-00 

 

Savant App Energy Modes

The following Energy Modes are supported according to the type of battery system installed.
 

BatteryEnergy Modes
SavantEco Mode, Power Outage Mode, and Storm Watch Mode
TeslaNormal Mode and Power Outage Mode
FranklinNormal Mode and Power Outage Mode
EnphaseNormal Mode and Power Outage Mode
Sol-ArkEco Mode, Off Grid Mode, Power Outage Mode, and Storm Watch Mode

 

 

Savant Flexible Load Management (FLM) with Generator Compatibility

The Savant Flexible Load Management system is compatible with all automatic generators with ATS auxiliary contacts to indicate switch position. When the Savant Flexible Load Management system is used with an automatic generator, the Power Modules will detect a grid outage using internal Zero Cross Detection and will immediately shed any non-critical loads. The system utilizes the position of the ATS (Grid or Emergency) to determine that the grid power has been restored. Upon grid restore, the ATS will qualify that grid power is stable and switch back to grid power. This will signal to the Power Module to restore power to their respective loads. (NOTE: system behavior upon grid restore can be modified during configuration if desired).

 

Grid Restore Detection Requirements

Grid restore detection is achieved by utilizing a set of auxiliary contacts in the ATS that change position (grid or emergency) and is connected to the GPIO on the Power Director. An example of an ATS with these contacts would be the ASCO 300 Series. Most ATS manufacturers, if not already present in the ATS, will have auxiliary contact kits that can be installed to provide the Savant Director with the ATS position. Contact the generator ATS manufacturer for more information.

In addition to using the ATS auxiliary contact to detect grid restore, use of a Current Track Module or a Smart Energy Monitor is required to monitor the main feed and report the total consumption of the home and generator output power. Savant also recommends Current Transformers (sized per the main feed), Current Track Modules, and a Smart Energy Monitor be installed into the main breaker panel.

 

 

Three Phase & Large Loads

The Savant Flexible Load Management system can support 120V/208V three phase loads or loads larger than 60A. This requires the following:

  • A 20A Power Module
  • Current Track Module or Smart Energy Monitor (SEM-2015)
  • A contactor with 120V coil.
  • Appropriate size/quantity of CTs (2 for 2-pole or 3 for 3-phase) rated for the size of the circuit(s)

The circuit is run from the circuit breaker through the contactor to the load. The 120V coil from the contactor is run through one of the channels on a 20A Power Module controlling the power to the coil, which opens and closes the circuit. There is no limit on circuit size; if the contactor has a 120V coil it can be controlled by a Savant Power Module.

Single Phase Loads

CTs used with either the Current Track Module or Smart Energy Monitor can be used to monitor and report the power useage to the Power Director.

Three Phase Loads

CTs used with the Smart Energy Monitor can be used to monitor and report the power usage to the Power Director.
NOTE: The Current Track Module cannot be used for three phase loads as it only supports 2 channels of monitoring.

 

 